PowerGATE ReadySwitchX
Installation Hole spacing
The X Series has (3) panel sizes based off of the product specifics, small, medium and large. Small Panel Size: Non-Service Entrance Rated: 100 Amp up to 600 VAC 200 Amp 120/208 VAC Service Entrance Rated: 100 Amp up to 600 VAC 200 Amp 120/208 VAC Medium Panel Size: Non-Service Entrance Rated: 200 Amp 480 to 600 VAC 400 Amp 120/208 VAC to 480 VAC
Prior to Installation: Site Preparation
Prepare installation site according to local codes. The ReadySwitch X Panel is to be secured to a building using appropriate 3/8 fasteners (See Figure 4, 5 & 6). The surface where the PowerGATE ReadySwitch is to be secured must be capable of supporting the weight of the cabinet as well as the cables attached to it. The following should be taken into consideration when locating the PowerGATE ReadySwitch X: - Identify and meet local codes and local Authority Having Jurisdiction (AHJ) - The PowerGATE ReadySwitchproduct line is designed for exterior operation ONLY - To prevent carbon monoxide poisoning from improperly ventilated generator emissions, the PowerGATE ReadySwitch X must be mounted outdoors only. The mounting location is to be carefully selected to allow convenient connection to a generator and located a suitable distance away from any building openings or HVAC inlets. - Proper clearance must be allowed in front of the ReadySwitch X switch to allow for opening of access doors and attachment of externally connected cables. This distance should be no less than six (6) feet from the face of the panel. - While padlock protection is provided, access by unauthorized personnel and vandals should be taken into consideration when locating this device.
Shipment: Unpacking and Inspection
NOTE: Be careful in the use of sharp object when cutting packaging as scratching of outer coating may result in rusting. Perform a visual inspection to ensure the door and handles are in functioning condition and that the panel integrity is intact.
Determining Your Part Number
Review Appendix F to verify part number, rating voltage, and amperage.
Figure 4 - Small Panel Hole Spacing Figure 5 - Medium Panel Hole Spacing