LEX PRODUCTS POWERGATE OUTPUT PANEL - SPECIFICATION BOILERPLATE 3.4.5. The upper termination chamber shall have a key lock handle door covering all exposed electrical parts. 3.4.6. The lower chamber main door shall have a key lock handle main door covering all exposed Cam-Type devices. 3.4.7. The lower chamber main door shall have a key lockable cable egress door to preventing unauthorized entry. 3.4.8. [ SPECIFY EITHER: No trap key provision OR panel shall have two (2) trap key provisions. 3.4.8.1. Output Panel with trap key provision shall come with two (2) 4X NEMA Rated, UL Listed hole seal. 3.4.8.2. Output Panel shall maintain cULus Listing with hole seal in place or trap key installed per installation instructions. 3.4.8.3. One (1) trap key provision is located on the Cam chamber access door. 3.4.8.4. One (1) trap key provision is located on the cable egress trap door. 3.4.9 [ SPECIFY EITHER: Bottom and top access feed for permanent connections OR Top access only. 4. ELECTRICAL 4.1. The output panel shall have output connections rated up to 600 VAC, as specified in the contract documents. 4.2. The lower chamber shall contain Series 16 Cam-Type devices. 4.2.1. All electrical devices shall be Cam-Type single pole devices, compatible with Marinco or Leviton 16 Series CAM Locks and available color coded as per industry standard practice: 4.2.2. 240V and below: phase 1 = black, phase 2 = red, phase 3 = blue (if required). 4.2.3. 440 to 480V: phase 1 = brown, phase 2 = orange, phase 3 = yellow. 4.2.4. Ground shall always be green. 4.2.5. Neutral shall always be white.