1 2 3 4 A B

ANY DESIGN OR MANUFACTURE EXCEPT WHOLE ORIN PART OR USEDFOR PRODUCTS CORP. REPRODUCED OR DISCLOSED IN WHEN SUCH USER POSSESSES CORP AND SHALL NOT BE IS PROPRIETARY TO LEX PRODUCTS .x

`0.03

DIMENSIONS ARE IN INCHES (mm) TOLERANCES UNLESS SPECIFIED: .xx

`

0.01 .xxx

`

0.005 THE INFORMATION CONTAINED HEREIN FRAC. `1/16 WRITTEN AUTHORIZATION FROM LEX

6/9/2017

DATE:

ANG.

`1/4~

2017 LEX PRODUCTS DRAWN BY:

jvalus

LEX PRODUCTS

11 Forest Parkway, Shelton, CT. 06484

PART NUMBER: TITLE:

SHEET 1 OF 4

000 PCS-T-A-MC-16

REV.

REVISION HISTORY REV DESCRIPTION DATE APPROVED 000 INITIAL RELEASE 6/9/2017 NOTES:

1) THE MODULE CHAMBER SHALL BE A FREE-STANDING, PORTABLE SWITCHBOARD PANEL RESPONSIBLE FOR SUPPORTING SIXTEEN (16) MODULES. 2) MODULE CHAMBERS SHALL BE FRAMED USING FORMED 0.10 SHEET ALUMINUM AND ENCLOSED USING 0.50 HIGH DENSITY POLYETHYLENE (HDPE) PANELS. 3) ENCLOSURE SHALL BE SUPPORTED ON FOUR (4) HEAVY-DUTY, LOCKING, SWIVEL CASTERS. 4) THE MODULE CHAMBER SHALL OPERATE AT A NOMINAL VOLTAGE OF 208Y/120 VAC 3-PHASE, 4-WIRE PLUS GROUND AT 60HZ. 5) THE MODULE CHAMBER SHALL FUNCTION AT ALL LOADS WITHOUT NOTICEABLE AFFECT PROVIDED THE TEMPERATURE OF THE AMBIENT AIR DOES NOT EXCEED 32

~

F TO 104

~

F (0

~

TO 40

~

C) RANGE. 6) LINE INPUT AND THRU POWER SHALL BE VIA SERIES 16 CAM-STYLE SINGLE-POLE CONNECTORS. 7) MULTI-CIRCUIT 19-PIN 20 AMP RECEPTACLES SHALL BE UTILIZED TO WITHDRAW LOAD POWER. 8) THE MODULE CHAMBER SHALL BE cULus LISTED.

PART LIST ITEM PART NUMBER DESCRIPTION REF DWG QTY A PCS-T-A-MC-16 PCS TRIO, TOURING, A-SERIES, MODULE CHAMBER, 16 MODULE - FRONT BACK 48.60 [123.44] 29.55 [75.06]