1 2 3 4 A B C D
US Pat. No. 7,136,278 B2
TM
PowerGATE
200 A Company Switch
FOR USE IN AREAS NOT READILY ACCESSIBLE BY THE GENERAL PUBLIC
FOR USE BY QUALIFIED PERSONNEL ONLY
THE ROUTING OF PORTABLE SUPPLY CONDUCTORS, THE MAKING AND BREAKING OF SUPPLY CONNECTORS, AND THE ENERGIZATION AND DE-ENERGIZATION OF SUPPLY SERVICES SHALL BE PERFORMED BY
QUALIFIED PERSONNEL ONLY.
LBL-CSQP
LBL-CSWRN C) UNGROUNDED CONDUCTOR CONNECTORS B) GROUNDED CIRCUIT CONDUCTOR CONNECTORS (NEUTRAL) A) EQUIPMENT GROUNDING CONNECTORS (GROUND)
RISK OF ELECTRICAL SHOCK
WARNING
DISCONNECTION MUST BE MADE IN REVERSE ORDER
A B C Ground
CS-200F-C6DS3-BLK
4
S N G B
5
Type 3R - Outdoor/Raintight Type 1 - Indoor Environmental Rating 3 1 Reverse Ground Reverse Both Gender Straight Reverse Neutral
3
Type 3R units may be used indoors
6 Wire Cam Type and Lugs 5 Wire Cam Type and Lugs Output Connections
6 Wire consists of a double neutral configuration
Company Switch Product Identity
1
CS (blank)
6
Black, matte Color/Finish -BLK Sand
1 2 3 5 6 4
C5D C6D 200F 100F 60F
2
Current Rating
Other current ratings available Consult Factory
60A 100A 200A
COMP SW 200A 6 WIRE STRAIGHT N3 BLK
LEX PRODUCTS
11 Forest Parkway, Shelton, CT. 06484
6/17/2020
DATE: DRAWN BY: TITLE:
Signature: Print Name:
RATING: PART NUMBER:
SHEET 1 OF 1
CS-200F-C6DS3-BLK
REV.
005
LEX PRODUCTS
Date: LEX Sales Order Number: Company:
THE INFORMATION CONTAINED HEREIN IS PROPRIETARY TO LEX PRODUCTS AND SHALL NOT BE REPRODUCED OR DISCLOSED IN WHOLE OR IN PART OR USED FOR ANY DESIGN OR MANUFACTURE EXCEPT WHEN SUCH USER POSSESSES WRITTEN AUTHORIZATION FROM LEX PRODUCTS.
Environmental Rating: Type 3R, Outdoor Dimensions: 20.27W /38.50L/9.33D Powder Coat Finish: [ ] Sand or [ ] Matte Black Wire range: (1) 500 KCM - 3/0 AWG per phase (2) 500 KCM - 4 AWG, Neutral (1) 500 KCM - 4 AWG, Ground Wire type: Aluminum/Copper gauged accordingly Output Connections: (6) Cam Type connectors, Double Neutral, Straight (6) Lugs for bare wire connection, in parallel with Cam Type connectors Rating: 208Y/120V, 2000A, 50/60Hz cULus Listed, E227821
BOTTOM VIEW
All output connectors are in this chamber behind a lockable door. Safety interlock will trip the breaker when the door is opened to prevent termination while connectors are live. Conduit entry from top only, at least 1" in from sides
9.07 12.91 20.27 38.50
Cover Plate Removed Cover Plate
14.00 37.22
n
.44 TYP 14.00 REVISION HISTORY REV DESCRIPTION DATE APPROVED 005 EC 3232 6/17/2020