DETAIL B SCALE 1 / 3
B
1 2 3 4 A B C D
C PART NUMBER: REV. TITLE: 2011 LEX PRODUCTS CORP.
15 Progress Drive, Shelton, CT 06484
LEX PRODUCTS CORP.
THE INFORMATION CONTAINED HEREIN IS PROPRIETARY TO LEX PRODUCTS REPRODUCED OR DISCLOSED IN WHOLE OR IN PART OR USED FOR ANY DESIGN OR MANUFACTURE EXCEPT WHEN SUCH USER POSSESSES WRITTEN AUTHORIZATION FROM LEX PRODUCTS CORP. CORP AND SHALL NOT BE
CS-100F-D5PS1 000
SHEET 1 OF 1
ENCLOSURE MATERIAL:
14GA CRS
Company: Name: Position:
Ap roved By
CHECKED BY: DRAWN BY:
DM 1/8
SCALE: DATE:
2012-05-023
QUOTE NO.:
Company Switch
US Pat. No. 7,136,278 B2
TM
PowerGATE
100 A Company Switch
FOR USE IN AREAS NOT READILY ACCESSIBLE BY THE GENERAL PUBLIC
FOR USE BY QUALIFIED PERSONNEL ONLY
THE ROUTING OF PORTABLE SUPPLY CONDUCTORS, THE MAKING AND BREAKING OF SUPPLY CONNECTORS, AND THE ENERGIZATION AND DE-ENERGIZATION OF SUPPLY SERVICES SHALL BE PERFORMED BY
QUALIFIED PERSONNEL ONLY.
LBL-CSQP
LBL-CSWRN C) UNGROUNDED CONDUCTOR CONNECTORS B) GROUNDED CIRCUIT CONDUCTOR CONNECTORS (NEUTRAL) A) EQUIPMENT GROUNDING CONNECTORS (GROUND)
RISK OF ELECTRICAL SHOCK
WARNING
DISCONNECTION MUST BE MADE IN REVERSE ORDER
A B C Ground
CS-100F-D5PS1 1 2 3 4
Other current ratings available Consult Factory
1 2 3 4
6 Wire consists of a double neutral configuration Type 3R units may be used indoors
5
Product Identity CS Company Switch Current Rating 100F 100A Output Connections C5DS Pin & Sleeve and Lugs C6DS Environmental Rating 1 Type 1 - Indoor 3 Type 3R - Outdoor/Raintight Color/Finish (blank) Sand -BLK Black, matte
Environmental Rating: Type 1, Indoor Dimensions: 20.27W /38.50L/9.33D Powder Coat Finish: [ ] Sand or [ ] Matte Black Contractor wiring: (1) 500 KCM - 3/0 AWG per phase (2) 500 KCM - 4 AWG, Neutral (1) 500 KCM - 4 AWG, Ground Output Connections: (1) Pin & Sleeve, 100A, 208Y/120VAC (H,H,H,N,G) (6) Lugs for bare wire connection, in parallel with Pin & Sleeve Connector Rating: 208Y/120V, 100A, 50/60Hz cULus Listed, E227821
20.27 14.00 11.64 9.26
n
.44 TYP BOTTOM VIEW
OSHA lockout/tagout compliant handle may be locked in the 'OFF' position (Locks not included).
14.00 38.50 REF 36.28
All output connectors are in this connection chamber behind a lockable door. Safety interlock will trip the breaker when the door is opened to prevent connections when connectors are live. Conduit entry from top only, at least 1" in from sides