1200-1600AMP: Construction Details
2000A - 4000A Panels Available by Request
cETLus Listed NEMA 3R for outdoor use in the U.S. and Canada
00A Panels by Request
Cable entry door provides limited access to CAM connections Designed for top or bottom feed entry Bus Bar made of 3/8" thick copper enable a short circuit capacity of 22,000 Amps Kirk Key provisions are provided for both cable entry door and CAM panel access door (See pg. 4 for more details) Auto/Remote Start contacts Phase Rotation Monitor CAM access panel for temporary generator PowerGATE 1200A - 1600A Power Input Panels have two separate lockable compartments. The top chamber has ample space for installing wiring from the permanent generator and the building electrical system. The bottom chamber is equipped with industry standard Cam-Type devices for easy connection when a temporary generator is required. Freestanding design eliminates structural stress associated with large wall-mounted panels