POWERGATE COMPANY SWITCH - SPECIFICATION (continued) 3 3.5. MAIN CIRCUIT BREAKER 3.5.1. The unit shall contain a single 3-pole [60Amp - OR - 100Amp - OR - 200Amp - OR - 400Amp] electronic circuit breaker. 3.5.2. The main breaker shall be 100% rated with a 65K AIC rating. 3.5.3. The main breaker shall be lockout-tagout equipped. 3.5.4. The main breaker shall be resettable to trip at 40% of its rated capacity. 4. INDICATORS 4.1. The Company Switch shall be equipped with light emitting diode indicator lights for each supply phase, labeled with an alphabetic description. 4.2. The unit shall be supplied with a light emitting diode indicator light indicating supply to ground continuity, labeled with an alphabetic description. 5. COMPLIANCE 5.1. The Company Switch must satisfy the requirements of NFPA 70 (National Electric Code) 5.1.1. Article 408 - Switchboards and Panelboards 5.1.2. Article 520 - Theaters, Audience Areas of Motion Picture and Television Studios and Similar Locations 5.1.3. Article 530 - Motion Picture and Television Studio and Similar Locations 5.2. Output panel connectors must specifically comply with: 5.2.1. Section 520.53(K) for Single-Pole Separable Connectors 5.2.2. Section 300.20(B) Induced Currents in Ferrous Metal Enclosures. 6. RECOGNITION 6.1. Panels shall be UL and cUL Listed. Labels shall be secured to the panel. 7. WARRANTY 7.1. The Company Switch shall carry a full two-year warranty from the time of shipment. 8. QUANTITIES 8.1. Provide Company Switches as scheduled. 9. APPROVED MANUFACTURER AND PRODUCTS 9.1. Switchboards shall be PowerGATE Company Switches, as manufactured by Lex Products, LLC of Shelton, CT.