POWERGATE COMPANY SWITCH - SPECIFICATION (continued) 2 3.3.3. The Company Switch shall contain a single 3-pole [ SPECIFY EITHER: 60 Amp OR 100 Amp OR 200 Amp OR 400 Amp] electronic circuit breaker. 3.3.4. The circuit breaker shall be 100% rated with a 65K AIC rating. 3.3.5. The circuit breaker shall be OSHA lockout/tagout equipped. 3.3.6. The circuit breaker shall be settable to trip at 40% - 100% of its rated capacity in the field. 3.4. OUTPUT 3.4.1. The Company Switch shall have output connections that contain both direct wire lugs and [ SPECIFY EITHER : Series 16 Cam-Type devices OR Series 18 Cam-Type devices OR a IEC 60309 pin-and-sleeve connector] for external connections. 3.4.1.1. Company Switches that have only one type of connection shall not be acceptable. 3.4.2. There shall be [ SPECIFY EITHER : five (5) cams/lugs OR six (6) cams/lugs OR one (1) IEC 60309 pin-and-sleeve/five (5) lugs]. 3.4.2.1. [ If cams/lugs, SPECIFY EITHER : Provide all female cam receptacles (straight) OR Provide female cam receptacles for the hot phases/ground and male receptacle(s) for the neutral (reverse neutral OR Provide female cam receptacles for the hot phases/neutral and male receptacle(s) for the ground (reverse ground) OR Provide female cam receptacles for the hot phases and male receptacle(s) for the ground(s)/neutral(s) (reverse both).] 3.4.2.2. [ If 6 cams/lugs, SPECIFY EITHER : Provide double ground cams/lugs OR Provide double neutral cams/lugs.] 3.4.3. Connections shall be arranged so that cables drape downward when connected. 3.4.4. Cables shall enter and exit the wiring chamber from access holes in the bottom of the enclosure. 3.4.5. A lockable hinged access door shall restrict access to the wiring chamber for safety and security. 3.4.5.1. The access door shall engage the shunt trip mechanism of the main circuit breaker whenever it is not fully closed, so that connections cannot be made or broken under load. 3.4.5.2. Company Switches that do not provide shunt trip protection of a wiring chamber shall not be acceptable. 3.4.6. The Company Switch shall provide a spring loaded strain relief for lug cables exiting the bottom of the chamber. 3.4.7. Output lug connections shall accommodate a maximum of 500MCM (300mm
2
) cable. 3.4.8. A strip of white light-emitting diodes (LEDs) shall light the wiring chamber whenever the access door is open. 3.4.9. [ OPTION ] The Ground connection shall be isolated from the frame.
Previous Page