LEX PRODUCTS POWERGATE INPUT PANEL - SPECIFICATION BOILERPLATE 4.3. 400 - 800 Amp Models 4.3.1. The upper termination chamber shall be provided with lug terminals for the permanently installed conductors. 4.3.2. The lower chamber shall have Cam-Type single pole devices as specified above. 4.3.2.1. 400A models: One (1) row of up to five (5) Series 16 Cam-Type single pole male devices. 4.3.2.2. 800A models: Two (2) rows of up to five (5) Series 16 Cam-Type single pole male devices. 4.3.3. Withstand Current Rating (WCR): No less than 10kA verified by supervised testing from a Nationally Recognized Testing Laboratory (NRTL), not by calculation. 4.3.4. [ SPECIFY EITHER: Phase Rotation Monitor and Two wire auto start OR None] 4.3.4.1. Input panels with phase rotation monitor shall have an overall rating of up to 480 VAC. 4.4. 1200 - 1600 Amp Models 4.4.1. The upper termination chamber shall have 0.375 (1.90 cm) copper buss bars with 0.50 (1.27 cm) holes drilled on 1.95 (4.95 cm) centers. 4.4.2 . The lower chamber shall have Cam-Type single pole devices as specified above. 4.4.2.1. 1200 Amp models: Three (3) rows of up to five (5) Series 16 Cam-Type single pole male devices. 4.4.2.1. 1600 Amp models: Four (4) rows of up to five (5) Series 16 Cam-Type single pole male devices. 4.4.3. Withstand Current Rating (WCR): No less than 22kA verified by supervised testing from a Nationally Recognized Testing Laboratory (NRTL), not by calculation. 4.4.5. [ SPECIFY EITHER: Phase Rotation Monitor and Two wire auto start OR None] 4.4.5.1. Input panels with phase rotation monitor shall have an overall rating of up to 480 VAC. 5. WARRANTY 5.1. The power input panel shall carry a full two-year warranty from the time of shipment.