1 2 3 4 A B
ANY DESIGN OR MANUFACTURE EXCEPT WHOLE OR IN PART OR USED FOR PRODUCTS CORP. REPRODUCED OR DISCLOSED IN WHEN SUCH USER POSSESSES CORP AND SHALL NOT BE IS PROPRIETARY TO LEX PRODUCTS .x
`0.03
DIMENSIONS ARE IN INCHES (mm) TOLERANCES UNLESS SPECIFIED: .xx
`
0.01 .xxx
`
0.005 THE INFORMATION CONTAINED HEREIN FRAC. `1/16 WRITTEN AUTHORIZATION FROM LEX
8/27/2020
DATE:
ANG.
`1/4~
2015 LEX PRODUCTS CORP. DRAWN BY:
jvalus
LEX PRODUCTS CORP.
15 Progress Drive, Shelton, CT. 06484
PART NUMBER: TITLE:
SHEET 1 OF 1
000
400A MTS In House
REV.
READYSWITCH X SERIES MANUAL TRANSFER SWITCH PXM01UN13-KE-K-AE
1 4 8 10 2 3 5 6 7 9 11 FRONT VIEW DOOR REMOVED MANUAL TRANSFER SWITCH ENVIRONMENTAL RATING: TYPE 3R (OUTDOOR USE) AMPERAGE RATING: ACCORDING TO PART NUMBERING VOLTAGE RATING: ACCORDING TO PART NUMBERING ENCLOSURE MATERIAL: ALUMINUM 5052, 0.1" THICK, POWDER COATED, ANSI 61 GRAY (STANDARD) DISCONNECT METHOD: DOUBLE THROW SWITCH OVERCURRENT PROTECTION: 200 AMP/ 400 AMP with 65 KAIC SHORT CIRCUIT CURRENT RATING: 35KA PERMANENT INPUT: COMPRESSION LUGS TEMPORARY INPUT: 16 SERIES CAMS OUTPUT: DUAL COMPRESSION LUGS WIRE SIZE: 2 AWG - 600 MCM cULus 1008 LISTED TRANSFER SWITCH
PRODUCT IDENTITY PX READYSWITCH X PANEL TRANSFER METHOD M MANUAL CURRENT RATING 02 200A 04 400A NEUTRAL LINE U UNBROKEN B BROKEN SERVICE ENTRANCE RATING S SERVICE RATED VOLTAGE TYPE 1 120/208 V 4 480/277 V 6 600/347 V ENVIROMENTAL RATING 3 NEMA 3R PRIMARY INPUT CONNECTOR K LUGS SECONDARY INPUT CONNECTOR E CAM TYPE (16 SERIES H,H,H,N,G) OUTPUT CONNECTOR K LUGS ACCESSORY CODE A (2) DUPLEXES B (2) GFCI DUPLXES C (1) L5-30 D NON GFCI BREAKERS E GFCI BREAKERS F STRIP HEATER G STAINLESS STEEL ENCLOSURE 1 2 3 4 5 6 7 8 9 1
0
11
ACCESS DOOR FOR ACCESSORY OUTLETS CAM INPUT PER CONFIGURATION ACCESSORY BREAKERS PHASE ROTATION MONITOR MTS HANDLE
READYSWITCH SERIES X SUBMITTAL DRAWING
WIRE SIZE AND TORQUE VALUE CHART CONNECTION WIRE SIZE TORQUE VALUE LINE SIDE,INPUT, HOT (200A BREAKER, LUGS) 6 AWG - 350 MCM 275 IN-LB LINE SIDE,INPUT, HOT (400A BREAKER, LUGS) 250 MCM - 500 MCM 380 IN-LB LOAD SIDE, OUTPUT, HOT & NEUTRAL & GROUND (MTS, LUGS) (2) 2 AWG - 600 MCM 375 IN-LB REVISION HISTORY REV DESCRIPTION DATE APPROVED 000 INITIAL RELEASE 8/9/2021 JVJR
200 AMP 480/600V & 400 AMP SERVICE ENTRANCE RATED VERSION
43.00
n
.40 TYP. 30.00 42.00 38.00 18.34 16.81